The Fundamentals of Heating and Cooling Degree Days, Part 2

7 Comments Read/write comments

balance degree day base temperature

Degree days are a combination of time and temperature. We looked at their uses and where they come from in part 1 of this series, and now it's time to go a little deeper. The temperature enters as a temperature difference, ΔT (delta T), but it's not the ΔT between inside and outside of the building. It's the difference between the outdoor temperature and the base temperature. But what is this thing called base temperature?

Base temperature defined

Let's start with the most general definition. The base temperature is the outdoor temperature that separates when the building needs heating or cooling from when it doesn't. If the outdoor temperature is higher than the base temperature, the building's heating system shouldn't have to operate to maintain the desired indoor temperature. If the outdoor temperature is at or below the base temperature, the building needs heat.

That's pretty straightforward. The base temperature is a balance point and has a nice, clear, conceptual meaning. It just doesn't correspond to an exact, constant number, which is how it's usually presented.

Factors that affect base temperature

I used 65° F as the base temperature in the previous article, but let's examine that choice. Why is it the baseline most often used in the US for heating degree days? According to the definition above, that would be the threshold at which you need to start adding heat to keep the building at a setpoint of about 68° F. (More on that discrepancy between base temperature and setpoint below.)

But in what building? With what kind of air and thermal control layers? How well is it shielded from changes in the outdoor environment? 65° F is probably about right for a building with a relatively weak level of air sealing and insulation. Maybe. Even a leaky, poorly insulated building won't need heating at 65° F if it's got a lot of internal heating loads (e.g., people or appliances). And a Passive House may be fine with just the internal loads down into the 30s or 40s Fahrenheit, perhaps even lower.

Here are a few of the factors that affect what the actual base temperature will be:

  • Indoor temperature. The warmer you keep it inside, the higher the base temperature will be.
  • Internal heat gains. Lights, appliances, and people add heat to the inside of the building. The more they add, the less your heating system needs to supply in winter and the lower the actual base temperature.
  • Rate of heat loss or gain. A building that loses heat faster in winter will have a higher base temperature than one that holds onto the heat. 
  • Season. Solar gains change throughout the year. Wind patterns change. How a building is used changes. Indoor setpoints change, too, because of the effects above but also because of varying mean radiant temperature. (Naked people need building science, you know.)

One interesting relationship came up when my cohort Jeffrey Sauls and I were discussing this topic. When you make a building enclosure more energy efficient with better insulation and air sealing, you reduce the heating base temperature. Jeffrey pointed out, however, that if you make the building more energy efficient by using more efficient lights and appliances, the heating base temperature goes up because the heating system has to do more of the work. If you do it right, the building enclosure improvements trump the light and appliance improvements by a lot.

We should probably be talking about two different base temperatures: actual and standard. The actual base temperature is the one defined above. The standard base temperature is the one commonly used, and it's not the same everywhere. In the US, we mostly use 65° F for heating degree days. In the UK, 15.5° C (60° F) is the standard base temperature.

Difference between base and indoor temperatures

I was a little confused when I first started thinking about degree days. As I showed in my previous article on the topic, you can put DD right into the heat flow equation (Q = U x A x ΔT), but in that equation, ΔT is the temperature difference between indoors and outdoors. The ΔT used in degree days is the temperature difference between outdoors and the base temperature.

In the US, we use 65° F as our base temperature, but we typically keep the indoor temperature at 70° F. Why don't we account for the other 5 degrees when we use degree days in the calculation?

incandescent light bulb ceiling fan internal heat gain

The answer goes back to the definition of base temperature. Recall, it's the balance point between needing the heating or cooling system to operate or not. If the temperature in heating season is above the base temperature but below the setpoint, the house is still losing heat through the building enclosure. It just doesn't need the heating system to make up for the heat loss because the internal gains (lights, appliances, and people) add enough heat to keep the house comfortable.

So, there is indeed a discrepancy between the two calculations. Using degree days, you get the amount of heat the heating system needs to add. Using ΔT as the temperature difference between indoors and outdoors, you get the amount of heat loss through the building enclosure, which is made up by both the heating system and the internal gains.

What are you using degree days for?

Despite these problems, having a uniform baseline is still good for some things. Being able to compare one climate to another is the main one. Since I know both numbers use the same baseline of 65° F, I can tell right away that the 14,000 HDD of Fairbanks, Alaska is much too cold a place for me. Give me Atlanta's 3000 HDD...with a few excursions to the 7000-9000 HDD skiing climates!

If you're doing calculations with degree days to determine the effectiveness of energy efficiency measures, it's probably worthwhile to, you need to choose a baseline appropriate to the building. Energy Lens, a UK firm that makes energy management software, has a great article about the intricacies of degree days. They also have one of the best sites for finding degree days for a lot of locations. It's called DegreeDays.net, and it allows you to generate degree days for whatever baseline you want to use.

Resolving the base temperature problem

As I mentioned in the previous section, if you're using degree days to compare climates, you don't need to do anything except make sure the numbers you're using all have the same base temperature. If you're doing degree day calculations, you want to use a base temperature as close to the actual base temperature as possible. With data loggers or even just paying a little bit of attention to when the heating and cooling system come on, you can do better than using the standard base temperatures.

The more important thing, though, is to keep in mind that you're not getting results to nearest BTU. Degree day calculations won't give you results to the nearest 100 BTU and probably not even to the nearest 1000 BTU no matter how good a job you do choosing the base temperature. It's an approximate calculation, and it's the relative changes that matter more than the numbers of British Thermal Units.

Doesn't mean it's not useful and can't be immensely helpful. It just means you need to keep it in perspective and understand the limits.

 

Related Articles

The Diminishing Returns of Adding More Insulation

What's Your Energy Efficiency Number?

We Are the 99% — Design Temperatures & Oversized HVAC Systems

 

Photo of ceiling fan by Charles Williams from flickr.com, used under a Creative Commons license.

 

Comments

Bob

Other factors that affect base temp are 
Wind chill and Solar gain. These are particularly troublesome to nail down into efficiency calculations. If it's morning before the sun comes up and windy my house may need heat when it's 60f degrees outdoors. If it's a sunny afternoon with no wind it may be 45f outdoors before I need heat. Base temp is a moving target that varies throughout the day. I've found 55f to be about right when doing year to year comparisons on my own house. 
 
When using the conventional 65f it threw my calculations WAY off when comparing a record cold winter to a normal winter. That's what led me to do more investigating on base temps.  
http://homeenergypros.lbl.gov/forum/topics/how-to-determine-hdd-s-and-sa...

David Eakin

To Bob's comment - that is why air temperature measurements (alone) are not a good measure of comfort regardless of what the Nest/Google people would have you think (that would be a different blog topic). Heating/cooling degree days are only good for comparing and measuring structure/system changes that affect energy use.

DIXIE WONG

Thanks for taking time to write this informative article during this BUSY SEASON. Many wishes for a rewarding CHRISTMAS and HAPPY NEW YEAR!

John Proctor

It is incumbent for us to remember that not only are the degree days for any location variable from year to year. They are also on an upward trend. An issue that we wish was not true, but is real. 
See slide 19 on the attached link 
http://www.proctoreng.com/dnld/Proctor-DatanotDogma.pdf

Rob Brown

Also, building mass, which is really overvalued for "R-value equivalence", DOES play a role here, as does the normal diurnal outdoor temperature swings. If you're in constant cold, that's different then cyclical excursions to temps below base temperature where the mass of the building can even things out. 
 
If I'm calculating for ICF or other massive constructions, I typically give a nod to my base temperature to reflect that ability of the building to temporarily even out the milder swing temperatures. 
 
I'd really love a simplified tool that allows a user to put in plug loads, building mass, design heat load, and zip code and have it run the building through a model year to give us a good estimate for DD base temperature.

Georg

So, is the absolute value of an HDD (or CDD) figure different depending on which temperature scale it is based on, leaving all other parameters unchanged? In other words, if an American quotes an HDD figure to a German, will the latter understand that figure, or will it have to be converted, just like °F has to be converted to °C?

Allison Bailes

Georg: Yes, degree days do depend on the temperature scale because Fahrenheit and Celsius degrees aren't the same size. For each 9° F there are 5° C. Likewise, for each 9 degree days based on Fahrenheit temperatures, there are 5 Celsius degree days.