We Are the 99% — Design Temperatures & Oversized HVAC Systems
We're making progress! With the all the emphasis on energy codes and energy efficiency programs like ENERGY STAR New Homes, more homes are getting Manual J heating and cooling load calculations these days. The intent is that the heating and cooling systems installed will be sized properly because oversized systems have problems (poor dehumidification, short cycling...). But just because an HVAC contractor does a Manual J, that's not a guarantee that the system is sized properly.
It's getting hot!
One of the ways that many HVAC systems get oversized is by someone using the wrong design temperatures in the load calculation. Here's the skinny:
- Homes lose heat to the outside in winter and gain heat from outside in summer.
- The rate of heat loss or gain depends on the temperature difference between inside and out.
- ASHRAE (a bunch of engineers who know a thing or two about HVAC) has a table of outdoor design temperatures for winter and summer.
- ACCA (the trade association for air conditioning contractors) bases its Manual J load calculation procedure on the ASHRAE design temperatures.
- Contractors running load calculations regulary override the recommended design temperatures.
The temperatures inside and outside your home are constantly changing. Sometimes the amount of heat your home loses or gains is low, and sometimes it's high. Even over the course of a day, the loads change. For example, we might hit a low of 70° F at night in the summer and a high of 96° F, and all through the day, the loads keep changing.
If we're trying to keep the indoor air at 75° F, the temperature difference is close to zero in the morning and rises to about 20° F in the afternoon. As the temperature difference (ΔT) changes, the cooling load changes. As it turns out, though, most air conditioners installed in homes cannot change the amount of cooling they provide when the temperature conditions change. Yes, some systems do have variable capacity, like mini-split heat pumps, but most are fixed capacity.
The 99% and the 1%
Enter ASHRAE's design temperatures. It turns out that if you have HVAC equipment with fixed capacity, this temperature will provide optimal performance. But what exactly is the ASHRAE design temperature?
Winter: 99% design temperature. This is the outdoor temperature that your locations stays above for 99% of all the hours in the year, based on a 30-year average. Turning it around, the outdoor air where you live is going to be colder than this temperature for only 1% of the hours in a year. That happens to be about 88 hours per year. In Atlanta, the 99% winter design temperature is 23° F.
Summer: 1% design temperature. Your location will go above this temperature only 1% of the hours in a year, again, based on a 30-year average. Here in Atlanta, that number is 91° F, so we go above that temperature for only about 88 hours in a year.
Occasionally, you'll run across something called the 97.5% and 2.5% design temperatures. It's not what you may think. Those numbers were defined differently and are not used anymore. Because the definitions were different, the temperatures are pretty close to the 99% and 1% design temperatures.
The difference between the outdoor design temperatures and the indoor design temperatures (70° F and 75° F) is the ΔT that should go into the load calculation.
In defense of HVAC contractors
HVAC contractors don't like to get called back because of comfort complaints, and oversizing solves many comfort complaints. Of course, HVAC contractors don't have control over the building envelope and usually don't know how much infiltration a house will have. Phil Mutz, one of the smart HVAC guys at Moncrief Heating & Air Conditioning in Atlanta, recently wrote about this issue:
Homes are rarely built as designed, meaning blocking/insulation/sealing almost always fall short of design. When the home is hot mid July months after a customer has moved in, the customer is calling and yelling at the HVAC guy... not the insulation guy.
With the testing and verification required in Georgia now, we should get a lot better at controlling some of these other issues for all homes. Programs like ENERGY STAR have required inspections, testing, and equipment sized to Manual loads for years now, so we do know this can work. As we get better data about the envelope, the loads in new homes will match the load calculations better, and HVAC contractors will stop being afraid to put in systems that they think are too small.
Check the numbers
Still, anyone getting a new home or doing extensive remodeling should insist on accurate Manual J load calculations and equipment that matches the loads. If you're a builder, homeowner, or HERS rater checking the Manual J reports, one of the first things you should look at are the outdoor design temperatures. The should match the 99% and 1% design temperatures from ASHRAE, which are also given in Table 1A in Manual J.
If the 1% summer design temperature is 91° F, as in Atlanta, a Manual J report showing that the load calculation was done with 97° F will result in an oversized air conditioner. Get your equipment sized for design loads, not extreme loads. Maybe it's getting hotter in recent years, but it's still best to use design temperatures based on 30-year averages — not the temperature it got to last summer for 3 hours.
Related Articles
Mr. Bean Proposes a Radical Change to Energy Codes The article above focuses on air temperatures, but mean radiant temperatures are critical, too. The first 3 articles here give some info about MRT.
Naked People Need Building Science
Thermal Comfort: Everyone Wants It but Few Know the ASHRAE Standard
Calculating Cooling Loads, by Martin Holladay at Green Building Advisor
Photo at top by Steve 2.0 from flickr.com, used under a Creative Commons license.