Air Barriers, Vapor Barriers, and Drainage Planes Do Different Jobs

Posted by Allison Bailes on Wed, Feb 5, 2014

Is housewrap a vapor barrier? What's the purpose of building paper? Who'll stop the rain? I've covered this topic in various forms before, but the confusion about what the different building materials do is so widespread that I have to keep coming back to it. I'm going to keep it simple here so maybe we can get a few more people to use the proper terms, and especially to know when not to use the term 'vapor barrier.'

Liquid-applied membrane for controlling air and liquid water at the building enclosure

Vocabulary, again

First of all, remember that the purpose of the building enclosure is to control the flows of water (liquid and vapor), air, and heat. We use different materials in buildings to accomplish the various levels of control we need, and of course, what you need in your building depends on your climate and what you're doing inside.

The term I like best to describe these materials is control layers. There's a liquid water control layer, a water vapor control layer, an air control layer, and a thermal control layer. That term helps unify the group.

They also have different names. As I wrote last week, the liquid water control layer is also called the drainage plane or the water-resistant barrier (WRB). The water vapor control layer is also called a vapor retarder or vapor barrier. The air control layer is also called an air barrier. The thermal control layer is also called insulation. Those terms probably aren't going away anytime soon.

Did you really mean to say 'vapor barrier'?

The biggest point of confusion seems to be about what a vapor barrier is. Most often, I hear people saying they need a vapor barrier when what they really mean is they need a liquid water control layer. Housewrap, to answer the question I opened with, is not generally a vapor barrier. Dupont's Tyvek Homewrap has a permeance of 58, putting it way into the vapor permeable range.

Peeling paint was one of the things that sent us down the wrong path of vapor barriers

As I wrote not that long ago, it's generally more important for building assemblies to be able to dry out than it is to stop water vapor from moving into them. We got on the wrong track with vapor barriers in the mid-twentieth century because of some incomplete science.

The 2 kinds of insulation

Another one I hear quite a bit is the confusion about what insulation does. Insulation comes in both air-permeable (like fiberglass or cellulose) and air-impermeable (like spray foam) forms. Putting in more fiberglass or cellulose insulation won't give you the airtightness you need in a house without additional air-sealing. They're thermal control layers but not air control layers. Spray foam insulation of the proper thickness is both.

One material, multiple levels of control

Housewrap, to stick with the most common material used as the liquid water control layer, is a material that can control the flow of liquid water as well as air. It's rarely installed well enough to be a good air barrier, but that's OK because in most homes it's stapled to a material that usually is: plywood or OSB. Housewrap is the material. Controlling liquid water and air are the functions. The standard varieties don't control water vapor or heat.

Open cell spray foam can control heat and air but not water vapor or liquid water. Closed cell foam can control heat, air, water vapor, and liquid water. Rigid foam insulation, depending on type and facings, also can control all four.

When you're looking at plans or actual building assemblies, go through material by material, layer by layer, and see if you can identify the functions of each. Is that material controlling heat, air, liquid water, or water vapor? Is it controlling more than one? Even if it's there for structural reasons, you need to know how it might affect the flows of heat, air, and moisture. OSB, for example, is vapor semi-permeable and can reduce an assembly's ability to dry.

Getting the building enclosure right is critical to the success of a building. Knowing this stuff is the key to getting the building enclosure right.


Related Articles

6 Materials That Drain the Rain on the Plane and Keep A House Dry

Be a Controlling Building Enclosure Control Freak with Control Layers

5 Reasons House Wrap Is Not an Air Barrier