skip to Main Content

The Confusing World of Dehumidifier Capacity

A Whole House Ducted Dehumidifier

Dehumidifiers have one job:  to turn water vapor into liquid water by moving air over a cold coil that’s below the dew point.  The capacity, or size, of a dehumidifier is just the rate at which it does that conversion.  It’s an easy concept to grasp and seems like it should be easy to measure, right?

You turn on the dehumidifier, let it run for a specific amount of time, and measure the amount of liquid water produced in that time.  The volume of water divided by the time is your capacity.  In the US, we use pints per day for this quantity, but any volumetric rate will do:  liters per hour, cubic meters per month, barrels per fortnight…

What kind of air are you dehumidifying?

A fair amount of complexity, however, is hiding behind that simple concept.  For example, what are the conditions of the air entering the dehumidifier?  If the air being dehumidified were 80° F and 60% relative humidity, you’d get one result.  If the air entering were 65° F and 60% relative humidity, you’d get a different result.  At 80° F and 60% relative humidity, there’s more moisture to remove than at 65° F and 60% relative humidity.

Go shopping for a room dehumidifier, and the most common capacity you’ll find is 30 pints per day.  That number is based on tests done according to rules set by the US Department of Energy (DOE)…or, I should say, a previous set of rules from the DOE.  That 30 pint per day dehumidifier almost certainly is rated at 30 pints per day using the 2012 rules, but the DOE issued new rules for testing capacity in 2020.

Under the new rules, that 30 pint per day dehumidifier is really a 20 pint per day dehumidifier.  What changed?  The temperature of the air used in the test.  The old test required the air being dehumidified to enter at 80° F and 60% relative humidity.  The new test requires 65° F and 60% relative humidity.  Less moisture in the air at the lower temperature means a lower dehumidification capacity.

2 types of dehumidifiers

Dehumidifiers are like people:  They come in two types.†  The two dehumidifier types are room (also called portable or standalone) and whole-house (also called ducted).  The main function of both types is the same, but the way they’re tested is different.  The DOE rule mentioned above (testing at 65° F and 60% relative humidity) is for room dehumidifiers.  For whole-house dehumidifiers,* it’s 73° F and 60% relative humidity.

Why?  I’ve been asking around and haven’t found the actual reason yet, but David Treleven with Madison Indoor Air Quality figures it’s because of the different ways room and whole-house dehumidifiers are used.  Room dehumidifiers usually sit in a cool basement, so they pull in cooler air.  (Occasionally someone doesn’t understand their limits and puts one in a vented crawl space.)  Whole-house dehumidifiers dehumidify the air from the main living space, which is generally warmer.

What you really need to know about dehumidifier capacity

Don’t get hung up on the rated capacity.  That number is a mirage, like air conditioner capacity, insulation R-value, and Energy Rating Index.  It’s a number based on specific test conditions that you won’t achieve in your house.  In addition to differing temperatures and relative humidities, you’ll also get different results if the dehumidifier cycles on and off versus running continuously.

And then there’s the issue of air flow affecting the capacity.  With room dehumidifiers, the air flow is constant whereas the air flow in a ducted dehumidifier* depends on the amount of resistance in the duct system.

Manufacturers aren’t doing much to change their marketing materials to reflect the new, lower capacities, at least not yet.  It doesn’t really matter, though.  The rated capacity matters only in how well it matches up with your dehumidification needs.  That takes us to the topic of sizing a dehumidifier, which I’ll cover soon.  (Hint:  It’s not like sizing an air conditioner.)

 

Allison Bailes of Atlanta, Georgia, is a speaker, writer, building science consultant, and founder of Energy Vanguard. He is also the author of the Energy Vanguard Blog and is writing a book. You can follow him on Twitter at @EnergyVanguard.

 

† One group of people, of course, sees everyone as being in one of two groups.  If that doesn’t sound like you, then you’re in the other group.

* This is an affiliate link. You pay the same price you would pay normally, but Energy Vanguard gets a small commission if you buy after using the link.

 

Related Articles

Make Dew Point Your Friend for Humidity

The Perfect Weather for a Dehumidifier

Accidental Dehumidification – A Preventable Mess

 

NOTE: Comments are moderated. Your comment will not appear below until approved.

This Post Has 6 Comments

  1. Get article, Allison. I have discussed this several times in my air conditioning class when we discus the psychrometric chart and in the weatherization class. At a recent webinar, I questioned a salesman about sizing and got a very vague answer. I am definitely interested reading your next article.

    1. Why is it that portable dehumidifiers are not built with an external window tube venting system to cool the compressor coils, similar to a portable A/C with window vents? As it is, the dehumidifier will heat the room causing discomfort and/or unnecessarily loading the Central A/C system.

  2. As usual, another great educational blog, & as usual, very grateful for sharing your expertise. Re:
    DOE using higher air temperature for rating whole-house dehumidifiers because: “Whole-house dehumidifiers dehumidify the AIR FROM THE MAIN LIVING SPACE, which is generally warmer.” I have a question: should DOE be considering different standards for differing dehumidification situations or climate, etc? Building science now rightly recommends ventilation of ‘energy-efficient’ tight buildings to achieve high quality indoor air . In many areas that ventilation air may often have extended periods of temperatures far above 60 degrees & very high moisture content requiring direct ducting into the dehumidifier to prevent raising indoor humidity above 50%. Climate change is exacerbating that situation for many areas & for more extended periods of time. So is the single DOE testing standard that useful any more? What say you?

    1. @Terry, no test procedure can ever be sufficient for sizing compression based systems due to the wide performance variation depending on operating conditions. As with AC and heat pump ratings, dehumidifier ratings are intended as a basis for making product comparisons, not for sizing equipment for a specific project!

      Mechanical designers should always refer to manufacturer performance data when sizing equipment. The fact that so many contractors don’t know any better (or don’t care) is indicative of how dysfunctional the residential HVAC industry is!

  3. Good point David Butler. & I agree it’s very difficult to find residential HVAC contractors with staff expertise on ventilation, IAQ, or filtration, let alone building science concepts. Another variant of my question: wouldn’t it be useful for the DOE to do at least 1 other rating of whole-house dehumidifiers for situations where the dehumidification is focused on dehumidifying incoming ventilation air rather than a focus solely on dehumidification of the ‘main living space air’ as now done? For instance, in my residential situation [BEFORE I decided I had to educate myself on building science & ventilation]: (1) using DOE ratings, the HVAC contractor decided we only needed 80 pint capacity to dehumidify ventilation air; (2) that was seriously inadequate for the 6 month humid season; (3) I ended up installing a 120 pint capacity dehumidifier which does a much better job, enabling me to ventilate more often while keeping indoor humidity under 50%. Even so, as climate change has increased the outdoor humidity levels & season, I still have days I have to shut down ventilation totally to avoid high indoor humidity.

    1. @Terry wrote: “…wouldn’t it be useful for the DOE to do at least 1 other rating of whole-house dehumidifiers for situations where the dehumidification is focused on dehumidifying incoming ventilation air…?”

      Dehumidifier capacity is largely a function of inlet dew point. If you duct outside air directly to the inlet as you suggest, the DoE test procedure as it currently exists would no longer apply, as you’ve gone well outside the assumptions baked into the procedure (and not just the incoming air metrics). It’s relatively rare to see a whole-house dehumidifier set up this way, but the next time the DoE updates its DH test procedure, maybe this will be a thing…?

      In any case, I come back to my original point: official rated capacity should not be used for sizing. Moreover, as I’m sure Allison will cover in his forthcoming article on sizing, DH capacity is only part of the puzzle — designers must also calculate moisture loads. This gets rather involved when the equipment is configured to directly condition outside air. This is the norm for commercial mechanical design.

      BTW, I would argue that designing to maintain RH below 50% in a humid climate, especially if t’stat is set below around 75F, imposes unnecessary expense, both in terms of first-cost & lifetime energy costs. The comfort range is generally accepted to be from 40% to 60% RH. To wit, most folks are equally comfortable at 55% as they are at 50%, and don’t tend to lower the t’stat to compensate until RH exceeds ~60%.

Comments are closed.

Back To Top