Eliminating Filter Bypass for Cleaner Air

A Huge Gap In This High-efficiency Filter Allows Dirty Air To Bypass The Filter

When it comes to the air moving through your HVAC system, filter bypass is not a good thing.  The lead photo above shows a bad case of bypass.  What you’re looking at is an old-style high-efficiency pleated filter.  I don’t recall the exact depth, but it was certainly 4 inches or more.  The big pleats were held apart by big combs (the black piece at the right side of the filter.  Either the installer didn’t pay close enough attention or the filter collapsed for some other reason.  The result, though, was a huge gap that allowed dirty air to bypass the filter.

Filter cabinets and grilles leak

The lead photo is unusual because that type of filter is uncommon.  But filter bypass is extremely common.  In my article about why filters often don’t improve indoor air quality, it was number 2 of the 7 reasons I gave.  The majority of HVAC systems seem to have 1 inch thick filters on the return side of the air handler.  They fit into a sheet metal slot and then another piece of sheet metal covers the slot.

But those covered slots are far from airtight.  The photo below shows a sizeable gap at the top of one such filter slot.  Because it’s right next to the blower, the negative pressure is highest right there.  That means any holes or gaps there will draw in more air than if they were farther from the blower.

Filter bypass through gaps in the cover
Filter bypass through gaps in the cover

Another common problem with this type of filter is that the cover is often missing.  That’s the case in the photo below…and many, many others that I’ve seen.

A filter installed with no cover, another common source of filter bypass
A filter installed with no cover, another common source of filter bypass

Some HVAC systems are in closets inside the house. (Hooray for being in conditioned space!)  On a trip to Florida, I saw one that had the poorly installed filter you see below.

Filter bypass around a poorly installed 1 inch fiberglass filter
Filter bypass around a poorly installed 1 inch fiberglass filter

Thicker filters with their own cabinets (like the ones AprilAire makes) are better for two reasons.  First, the thicker filter is harder to bend like the one just above.  Second, the cabinets are made to reduce bypass.  The filter fits tightly, and the door and perimeter of where the filter sits have weatherstripping.

And that brings me to…

What about weatherstripping?

I haven’t tested or seen evidence of filter bypass in weatherstripped cabinets like the ones made by AprilAire.  Nor have I looked.  But I do have some experience with weatherstripping.

I’ve written several times about the high-efficiency filters in my house (most recently here).  When I first got the system installed, I followed John Semmelhack‘s lead and used blue painters’ tape in the filter grille to eliminate bypass (photo below).

Clean MERV-13 filter in dining room, taped into filter grille
Clean MERV-13 filter taped into the filter grille in a central return vent

But taping a filter into a filter grille in a ceiling is a bit of a hassle.  Taping takes more time than just popping the filter in there.  It’s also difficult in a ceiling because of the weakest of the fundamental forces in the universe—this little thing called gravity.  So a couple of years ago, I installed weatherstripping in my filter grilles (photo below).

A ceiling filter grille with weatherstripping (black strips) to stop filter bypass.
A ceiling filter grille with weatherstripping (black strips) to stop filter bypass.

It made filter changes a lot easier.  But how well has it worked?

Dust on and above the weatherstripping in my filter grille
Dust on and above the weatherstripping in my filter grille

Well, I just changed the filters a few days ago, and you can see above that there’s quite a bit of dust on the weatherstripping and the filter grille housing above the weatherstripping.  That means I’ve got filter bypass because of the weatherstripping.  What you see is the dirt that gut stuck there.  I’m sure there was more that kept going all the way to the blower and coil of my heat pump.  The dirt you see is what has accumulated over the 2.5 years since I put the weatherstripping in.

Tape is the winner

After removing the dust I found there, I installed new filters.  I didn’t remove the weatherstripping because it does a great job holding the filter in place.  But I did go back to taping around the edges again.  Now my ducts, blower, and coil should stay cleaner.

Electrical bypass can be dangerous
Electrical bypass can be dangerous.

And by the way, there’s another kind of bypass that’s worse than filter bypass.  When you put conductors in an electrical system where you should have fuses, it can be really dangerous.  The photo above shows such a thing.  Those pieces of metal pipe can cause a fire or worse.

Building science lies: That gunk on your air conditioner isn't algae
That gunk on your air conditioner coil wouldn’t be there if you had an airtight duct system with no filter bypass.

But back to filter bypass now.  You don’t want it because it can make the ducts, blower, air conditioner coil, and furnace heat exchanger dirty.  Some of those indoor air pollutants may make it all the way through the system and back into your indoor air.  And a dirty coil can lead to microbial growth (photo above).  The goal for filtration is to have all the air pass through a high-efficiency filter (MERV 13).  That keeps everything clean, including your respiratory system.

 

Allison A. Bailes III, PhD is a speaker, writer, building science consultant, and the founder of Energy Vanguard in Decatur, Georgia.  He has a doctorate in physics and is the author of a bestselling book on building science.  He also writes the Energy Vanguard Blog.  For more updates, you can follow Allison on LinkedIn and subscribe to Energy Vanguard’s weekly newsletter and YouTube channel.

 

Related Articles

7 Reasons Your Filter Isn’t Improving Your Indoor Air Quality

The Advantages of Filter Grilles for Your HVAC System

How to Make a Good High-MERV Filter Even Better

 

Comments are welcome and moderated.  Your comment will appear below after approval.  To control spam, we close comments after one year.

This Post Has 6 Comments

  1. 2 observations:

    1. In the previous apartment where I lived, I saw the indoor coil being replaced after at least a decade of use. It was surprisingly clean considering that it had only been protected by the cheapest fiberglass filters which were never taped.

    2. In my current house, I installed gaskets that look identical to yours, but they slowly migrated out of place, so like you, I resorted to tape.

    1. Tim: Thanks for your comment. A lot of factors affect how dirty a coil can get over time: runtime, frequency of changing, pets, return duct leakage… Even a 1 inch fiberglass filter catches a lot of dirt and can keep things relatively clean if it’s changed often enough. But a lot of PM2.5 can go right through the whole system.

  2. As a North Carolina Home Inspector the condition of the return air duct is important to us. It’s much more than “Is the filter clogged?” In training we were taught that dust + condensation on the coil can ruin the system. It’s not just the healthy air. It’s the slime acting like insulation on the coil surface, which can block heat transfer and ruin the system in more ways than one. I just wrote this up yesterday in a report.

  3. I wish homeowners had some “basic training” on systems in their homes because simple maintenance can be so helpful in improving equipment efficiency and extending the lifespan. I appreciate your posts because with clear descriptions of the problem and the photos, people can see what to look for. Keep up the good work.

  4. “As you point out, dirty air going across a wet coil is much worse than it going across a dry coil.” Could this justify using cheaper filters during the heating season than the cooling season?

Comments are closed.

Back To Top